Single Core Cables, with stranded Circular Copper conductors, XLPE insulated, Aluminum wire armored, and PVC Sheath. 3.6/6 (7.2)

  • Stranded circular compacted copper conductor, Semi-conducting layer as conductor screen, XLPE insulated, semi-conducting layer as non-metallic insulation screen, copper tape or wire as a metallic screen, wrapped with binder tape, covered with a layer of PVC as bedding layer, Aluminum wire armored and PVC sheathed.

 

  • Cables are produced according to IEC 60502-2 or BS6622.

.

Summary of cables specifications
CT14XB01X1 Single Core
Copper
XLPE
50 0.387 0.4937 - - 211 210 169 238 242 - 24.5 1045 0.32 - 0.4129 0.4592 PVC
AWA
CT15XB01X1 Single Core
Copper
XLPE
70 0.268 0.3421 - - 258 256 208 295 299 - 26.4 1300 0.3735 - 0.3862 0.4324 PVC
AWA
CT16XB01X1 Single Core
Copper
XLPE
95 0.193 0.2467 - - 307 304 248 357 360 - 27.8 1580 0.4072 - 0.3741 0.4203 PVC
AWA
CT17XB01X1 Single Core
Copper
XLPE
120 0.153 0.1959 - - 346 343 282 410 411 - 29.2 1860 0.4464 - 0.3605 0.4068 PVC
AWA
CT18XB01X1 Single Core
Copper
XLPE
150 0.124 0.1591 - - 387 382 317 465 463 - 30.8 2160 0.4856 - 0.3503 0.3965 PVC
AWA
CT19XB01X1 Single Core
Copper
XLPE
185 0.0991 0.1277 - - 434 426 358 532 523 - 33.2 2620 0.5331 - 0.3399 0.3862 PVC
AWA
CT20XB01X1 Single Core
Copper
XLPE
240 0.0754 0.0979 - - 496 480 413 622 604 - 35.6 3230 0.6001 - 0.3256 0.3718 PVC
AWA
CT30XB01X1 Single Core
Copper
XLPE
300 0.0601 0.079 - - 555 528 465 709 679 - 38.6 3885 0.6492 - 0.3156 0.3618 PVC
AWA
CT40XB01X1 Single Core
Copper
XLPE
400 0.047 0.063 - - 620 579 525 808 762 - 41.8 4795 0.6722 - 0.3078 0.354 PVC
AWA
CT50XB01X1 Single Core
Copper
XLPE
500 0.0366 0.0505 - - 674 608 581 909 830 - 47 6195 0.7107 - 0.3039 0.3501 PVC
AWA
CT60XB01X1 Single Core
Copper
XLPE
630 0.0283 0.041 - - 738 654 644 1019 911 - 50.9 7635 0.7908 - 0.2954 0.3417 PVC
AWA
CT70XB01X1 Single Core
Copper
XLPE
800 0.0221 0.0343 - - 798 694 705 1130 991 - 55.6 9595 0.8917 - 0.2861 0.3323 PVC
AWA

 

These cables are generally suitable for direct burial or for installation on trays or in ducts.

  • IEC 60502-2
  • BS 6622

Download the full specifications PDF for more info
SPECS PDF