Multi Core Cables, with stranded Circular Copper conductors, XLPE insulated, Steel wires armored and PVC Sheath. 6/10 (12)

  • Stranded circular compacted copper conductor, Semi-conducting layer as conductor screen, XLPE insulated, semi-conducting layer as non-metallic insulation screen, copper tape or wire as a metallic screen, Multicores are assembled together with non-hygroscopic polypropylene fillers and wrapped with binder tape, covered with a layer of PVC as bedding layer, Steel wire armored and PVC sheathed.

 

  •  Cables are produced according to IEC 60502-2 or BS6622.

 

.

Summary of cables specifications
CT14X201X1 Multicore
Copper
XLPE
50 0.387 0.4937 - - 211 210 170 239 243 - 25.9 1115 0.263 - 0.4241 0.4703 PVC
AWA
CT15X201X1 Multicore
Copper
XLPE
70 0.268 0.3421 - - 258 256 209 297 301 - 28 1390 0.3051 - 0.398 0.4442 PVC
AWA
CT16X201X1 Multicore
Copper
XLPE
95 0.193 0.2466 - - 306 304 250 359 362 - 292 1665 0.3315 - 0.3839 0.4301 PVC
AWA
CT17X201X1 Multicore
Copper
XLPE
120 0.153 0.1958 - - 345 342 284 414 413 - 31.3 2000 0.3623 - 0.3744 0.4207 PVC
AWA
CT18X201X1 Multicore
Copper
XLPE
150 0.124 0.159 - - 386 381 319 468 465 - 32.9 2310 0.3931 - 0.3635 0.4097 PVC
AWA
CT19X201X1 Multicore
Copper
XLPE
185 0.0991 0.1276 - - 434 425 360 534 525 - 34.6 2710 0.4303 - 0.3482 0.3944 PVC
AWA
CT20X201X1 Multicore
Copper
XLPE
240 0.0754 0.0979 - - 496 479 416 624 605 - 37.2 3345 0.4828 - 0.3344 0.3806 PVC
AWA
CT30X201X1 Multicore
Copper
XLPE
300 0.0601 0.0789 - - 555 527 468 711 681 - 39.8 3975 0.5396 - 0.3217 0.368 PVC
AWA

 

These cables are generally suitable for direct burial or for installation on trays or in ducts.

  • IEC 60502-2
  • BS 6622

Download the full specifications PDF for more info