Single Core Cables, with stranded Circular Aluminum conductors, XLPE insulated, Aluminum wire and PVC Sheath. 6/10 (12)

  • Stranded circular compacted Aluminum conductor, Semi-conducting layer as conductor screen, XLPE insulated, semi-conducting layer as non-metallic insulation screen, copper tape or wire as a metallic screen, wrapped with binder tape, covered with a layer of PVC as bedding layer, Aluminum wire armored and PVC sheathed.

 

  • Cables are produced according to IEC 60502-2 or BS6622.

 

.

Summary of cables specifications
AT14X201X1 Single Core
Aluminum
XLPE
50 0.641 0.822 - - 164 163 132 186 190 - 25.9 830 0.263 - 0.4241 0.4703 PVC
AWA
AT15X201X1 Single Core
Aluminum
XLPE
70 0.443 0.5682 - - 200 200 162 232 236 - 27.7 960 0.2985 - 0.4018 0.4481 PVC
AWA
ATI 6X201X1 Single Core
Aluminum
XLPE
95 0.32 0.4106 - - 238 238 195 280 284 - 29.2 1085 0.3315 - 0.3839 0.4301 PVC
AWA
AT17X201X1 Single Core
Aluminum
XLPE
120 0.253 0.3248 - - 271 269 223 324 327 - 31.3 1270 0.3623 - 0.3744 0.4207 PVC
AWA
AT18X201X1 Single Core
Aluminum
XLPE
150 0.206 0.2647 - - 302 300 250 367 369 - 32.9 1415 0.3931 - 0.3635 0.4097 PVC
AWA
AT19X201X1 Single Core
Aluminum
XLPE
185 0.164 0.211 - - 342 338 284 420 420 - 34.6 1580 0.4303 - 0.3482 0.3944 PVC
AWA
AT20X201X1 Single Core
Aluminum
XLPE
240 0.125 0.1613 - - 394 388 330 494 490 - 37.1 1850 0.4806 - 0.335 0.3812 PVC
AWA
AT30X201X1 Single Core
Aluminum
XLPE
300 0.1 0.1296 - - 442 433 374 566 555 - 39.5 2115 0.533 - 0.3226 0.3688 PVC
AWA
AT40X201X1 Single Core
Aluminum
XLPE
400 0.0778 0.1016 - - 495 474 424 652 626 - 43.6 2635 0.5919 - 0.3162 0.3624 PVC
AWA
AT50X201X1 Single Core
Aluminum
XLPE
500 0.0605 0.08 - - 557 524 482 750 707 - 47.5 3145 0.6682 - 0.3067 0.353 PVC
AWA
AT60X201 XI Single Core
Aluminum
XLPE
630 0.0469 0.0634 - - 623 574 544 856 794 - 51.4 3760 0.7444 - 0.2977 0.3439 PVC
AWA
AT70X201X1 Single Core
Aluminum
XLPE
800 0.0367 0.0513 - - 690 623 610 974 886 - 56.4 4540 0.8488 - 0.2866 0.3328 PVC
AWA

 

These cables are generally suitable for direct burial or for installation on trays or in ducts.

  • IEC 60502-2
  • BS 6622

Download the full specifications PDF for more info
SPECS PDF