Single Core Cables, with stranded Circular copper conductors, XLPE insulated, Aluminum Wire armored and PVC Sheath. 8.7/15 (17.5)

  • Stranded circular compacted copper conductor, Semi-conducting layer as conductor screen, XLPE insulated, semi-conducting layer as non-metallic insulation screen, copper tape or wire as a metallic screen, wrapped with binder tape, covered with a layer of PVC as bedding layer, Aluminum wire armored and PVC sheathed.

 

  • Cables are produced according to IEC 60502-2 or BS6622.

-

Summary of cables specifications
CT14X301X1 Single Core
Copper
XLPE
50 0.387 0.4937 - - 210 209 172 242 245 - 28.3 1245 0.2104 - 0.4418 0.488 PVC
AWA
CT15X301X1 Single Core
Copper
XLPE
70 0.268 0.3421 - - 256 255 211 300 303 - 30.4 1525 0.2421 - 0.4144 0.4606 PVC
AWA
CT16X301X1 Single Core
Copper
XLPE
95 0.193 0.2466 - - 306 303 253 364 365 - 32.1 1850 0.262 - 0.4028 0.4491 PVC
AWA
CT17X301X1 Single Core
Copper
XLPE
120 0.153 0.1958 - - 345 341 287 417 416 - 33.7 2150 0.2851 - 0.3892 0.4354 PVC
AWA
CT18X301X1 Single Core
Copper
XLPE
150 0.124 0.159 - - 385 380 322 471 468 - 35.1 2450 0.3081 - 0.3764 0.4227 PVC
AWA
CT19X301X1 Single Core
Copper
XLPE
185 0.0991 0.1275 - - 432 423 363 536 527 - 37 2880 0.336 - 0.3616 0.4078 PVC
AWA
CT20X301X1 Single Core
Copper
XLPE
240 0.0754 0.0978 - - 495 479 419 628 609 - 39.4 3495 0.3752 - 0.3459 0.3921 PVC
AWA
CT30X301 XI Single Core
Copper
XLPE
300 0.0601 0.0788 - - 554 526 472 714 684 - 42 4125 0.4177 - 0.3325 0.3787 PVC
AWA
CT40X301 XI Single Core
Copper
XLPE
400 0.047 0.0627 - - 608 562 525 805 749 - 46.2 5220 0.46 - 0.3278 0.374 PVC
AWA
CT50X301X1 Single Core
Copper
XLPE
500 0.0366 0.0503 - - 674 608 587 913 835 - 50 6465 0.5153 - 0.3163 0.3625 PVC
AWA
CT60X301 XI Single Core
Copper
XLPE
630 0.0283 0.0407 - - 739 655 650 1023 916 - 53.7 7900 0.5713 - 0.3061 0.3524 PVC
AWA
CT70X301 XI Single Core
Copper
XLPE
800 0.0221 0.034 - - 801 695 712 1136 996 - 58.4 9895 0.6419 - 0.2959 0.3421 PVC
AWA

 

These cables are generally suitable for direct burial or for installation on travs or in ducts.

  • IEC 60502-2
  • BS 6622

Download the full specifications PDF for more info