Single Core Cables, with stranded Circular copper conductors, XLPE insulated, Aluminum wire armored and PVC Sheath.12/20 (24)

  • Stranded circular compacted copper conductor, Semi-conducting layer as conductor screen, XLPE insulated, semi-conducting layer as non-metallic insulation screen, copper tape or wire as a metallic screen, wrapped with binder tape, covered with a layer of PVC as bedding layer, Aluminum wire armored and PVC sheathed.

 

  • Cables are produced according to IEC 60502-2 or BS6622.

.

Summary of cables specifications
CT14X401X1 Single Core
Copper
XLPE
50 0.387 0.4937 - - 210 209 174 244 247 - 30.5 1365 0.1812 - 0.4567 0.503 PVC
AWA
CT15X401X1 Single Core
Copper
XLPE
70 0.268 0.3421 - - 256 254 214 303 306 - 33.1 1705 0.2072 - 0.4314 0.4777 PVC
AWA
CT16X401X1 Single Core
Copper
XLPE
95 0.193 0.2466 - - 305 302 255 366 366 - 34.3 1990 0.2235 - 0.4161 0.4623 PVC
AWA
CT17X401X1 Single Core
Copper
XLPE
120 0.153 0.1957 - - 344 340 290 419 418 - 35.9 2295 0.2424 - 0.4019 0.4481 PVC
AWA
CT18X401X1 Single Core
Copper
XLPE
150 0.124 0.159 - - 384 379 325 473 468 - 37.3 2600 0.2612 - 0.3886 0.4348 PVC
AWA
CT19X401X1 Single Core
Copper
XLPE
185 0.0991 0.1275 - - 431 422 366 539 530 - 39 3015 0.2839 - 0.3721 0.4184 PVC
AWA
CT20X401X1 Single Core
Copper
XLPE
240 0.0754 0.0977 - - 494 478 423 630 611 - 41.4 3635 0.3159 - 0.3558 0.402 PVC
AWA
CT30X401X1 Single Core
Copper
XLPE
300 0.0601 0.0786 - - 545 514 472 712 675 - 45.6 4485 0.3505 - 0.349 0.3952 PVC
AWA
CT40X401X1 Single Core
Copper
XLPE
400 0.047 0.0625 - - 608 562 529 808 753 - 48.4 5410 0.385 - 0.3371 0.3833 PVC
AWA
CT50X401X1 Single Core
Copper
XLPE
500 0.0366 0.0501 - - 674 608 591 914 834 - 52.2 6685 0.43 - 0.3249 0.3711 PVC
AWA
CT60X401X1 Single Core
Copper
XLPE
630 0.0283 0.0406 - - 740 655 654 1026 921 - 55.9 8130 0.4755 - 0.3412 3604 PVC
AWA
CT70X401X1 Single Core
Copper
XLPE
800 0.0221 0.0338 - - 803 697 717 1140 1002 - 60.6 10125 0.5329 - 0.3033 0.3495 PVC
AWA

 

These cables are generally suitable for direct burial or for installation on trays or in ducts.

  • IEC 60502-2
  • BS 6622

Download the full specifications PDF for more info
SPECS PDF