Single Core Cables, with stranded Circular Aluminum conductors, XLPE insulated, and LSHF Sheath. 8.7/15 (17.5)
|
.
Summary of cables specifications
AT14X301UL |
Single Core |
Aluminum |
XLPE |
50 | 0.641 | 0.822 | - | - | 166 | 167 | 129 | 179 | 184 | - | 22.2 | 555 | 0.2104 | - | 0.3932 | 0.4394 |
LSHF |
Unarmored |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AT15X301UL |
Single Core |
Aluminum |
XLPE |
70 | 0.443 | 5682 | - | - | 201 | 202 | 160 | 225 | 231 | - | 24 | 660 | 0.2371 | - | 0.3732 | 0.4194 |
LSHF |
Unarmored |
AT16X301UL |
Single Core |
Aluminum |
XLPE |
95 | 0.32 | 0.4106 | - | - | 243 | 245 | 191 | 273 | 280 | - | 25.5 | 770 | 0.262 | - | 0.3568 | 0.403 |
LSHF |
Unarmored |
AT17X301UL |
Single Core |
Aluminum |
XLPE |
120 | 0.253 | 0.3249 | - | - | 275 | 283 | 220 | 316 | 324 | - | 27.1 | 885 | 0.2851 | - | 0.3456 | 0.3918 |
LSHF |
Unarmored |
AT18X301UL |
Single Core |
Aluminum |
XLPE |
150 | 0.206 | 0.2648 | - | - | 309 | 313 | 247 | 359 | 369 | - | 28.5 | 995 | 0.3081 | - | 0.3348 | 0.381 |
LSHF |
Unarmored |
AT19X301UL |
Single Core |
Aluminum |
XLPE |
185 | 0.164 | 0.2111 | - | - | 350 | 351 | 282 | 414 | 426 | - | 30.4 | 1155 | 0.336 | - | 0.3223 | 0.3685 |
LSHF |
Unarmored |
AT20X401UL |
Single Core |
Aluminum |
XLPE |
240 | 0.125 | 0.1615 | - | - | 406 | 405 | 333 | 491 | 505 | - | 32.9 | 1385 | 0.3736 | - | 0.3109 | 0.3572 |
LSHF |
Unarmored |
AT40X401UL |
Single Core |
Aluminum |
XLPE |
400 | 0.0778 | 0.1019 | - | - | 522 | 516 | 439 | 661 | 675 | - | 38.2 | 1950 | 0.4568 | - | 0.2898 | 0.336 |
LSHF |
Unarmored |
AT60X401UL |
Single Core |
Aluminum |
XLPE |
630 | 0.0469 | 0.0639 | - | - | 678 | 687 | 583 | 901 | 912 | - | 45.8 | 2910 | 0.5705 | - | 0.2746 | 0.3209 |
LSHF |
Unarmored |
AT70X401UL |
Single Core |
Aluminum |
XLPE |
800 | 0.0367 | 0.0519 | - | - | 762 | 786 | 671 | 1042 | 1024 | - | 51 | 3630 | 0.6484 | - | 0.2665 | 0.3127 |
LSHF |
Unarmored |
These cables are generally suitable for direct burial or for installation on trays or in ducts.