Multicore Cables, with Stranded Copper Conductors, PVC Insulated, Armored by Steel Tape and PVC Sheathed. 0.6/1 (1.2) kV

  • Multicore cables of stranded Copper conductors are insulated with a PVC compound rated °70C, assembled together, armored with a steel tape, and covered with an overall jacket of a PVC compound.
  • Cables are produced according to IEC 60502-1.

.

Summary of cables specifications
CT12P102A1 Two Core Cables
Copper
PVC
25 r 0.727 0.87 - 124 96 133 22 1030 PVC
STA
CT13P102A1 Two Core Cables
Copper
PVC
35 r 0.524 0.628 - 147 119 164 24.2 1295 PVC
STA
CT11P103A1 Three Core Cables
Copper
PVC
16 r 1.15 1.39 - 85 68 83 20.6 860 PVC
STA
CT12P103A1 Three Core Cables
Copper
PVC
25 r 0.727 0.87 - 113 90 108 23.8 1200 PVC
STA
CT13P103A1 Three Core Cables
Copper
PVC
35 r 0.524 0.628 - 136 107 127 26.2 1530 PVC
STA
CT11P104A1 Four Core Cables
Copper
PVC
16 r 1.15 1.39 - 85 68 83 22.3 1070 PVC
STA
CT12P104A1 Four Core Cables
Copper
PVC
25 r 0.727 0.87 - 113 90 108 25.9 1520 PVC
STA
CT13P104A1 Four Core Cables
Copper
PVC
35 r 0.524 0.628 - 136 107 127 28.6 1950 PVC
STA
CT14P104A1 Four Core Cables
Copper
PVC
50 s 0.387 0.464 - 164 130 159 32.7 2640 PVC
STA
CT15P104A1 Four Core Cables
Copper
PVC
70 s 0.268 0.322 - 198 164 197 37.5 3915 PVC
STA
CT16P104A1 Four Core Cables
Copper
PVC
95 s 0.193 0.232 - 237 186 240 42.4 5140 PVC
STA
CT17P104A1 Four Core Cables
Copper
PVC
120 s 0.153 0.185 - 271 220 278 46.2 6310 PVC
STA
CT18P104A1 Four Core Cables
Copper
PVC
150 s 0.124 0.151 - 305 249 316 50.9 7615 PVC
STA
CT19P104A1 Four Core Cables
Copper
PVC
185 s 0.0991 0.121 - 339 277 361 56.1 9365 PVC
STA
CT20P104A1 Four Core Cables
Copper
PVC
240 s 0.0754 0.084 - 390 328 430 62.6 12790 PVC
STA
CT30P104A1 Four Core Cables
Copper
PVC
300 s 0.0601 0.077 - 441 362 506 68.7 14645 PVC
STA
CT40P104A1 Four Core Cables
Copper
PVC
400 s 0.047 0.0606 - 502 421 575 74.9 18510 PVC
STA
CT13P105A1 Four Core Cables with Reduced Neutral
Copper
PVC
35 sm + 16 rm 0.5240/1.1500 0.6280/1.3900 - 136 107 127 27 1740 PVC
STA
CT14P105A1 Four Core Cables with Reduced Neutral
Copper
PVC
50 sm + 25 rm 0.3870/0.7270 0.4640/0.8700 - 164 130 159 30.9 2365 PVC
STA
CT15P105A1 Four Core Cables with Reduced Neutral
Copper
PVC
70 sm + 35 rm 0.2680/0.5240 0.3220/0.6280 - 198 164 197 34.6 3155 PVC
STA
CT16P105A1 Four Core Cables with Reduced Neutral
Copper
PVC
95 sm + 50 sm 0.1930/0.3870 0.2320/0.4640 - 237 186 240 40.7 4625 PVC
STA
CT17P105A1 Four Core Cables with Reduced Neutral
Copper
PVC
120 sm + 70 sm 0.1530/0.2680 0.1850/0.3220 - 271 220 278 44.5 5730 PVC
STA
CT18P105A1 Four Core Cables with Reduced Neutral
Copper
PVC
150 sm + 70 sm 0.1240/0.2680 0.1510/0.3220 - 305 249 316 48.5 6740 PVC
STA
CT19P105A1 Four Core Cables with Reduced Neutral
Copper
PVC
185 sm + 95 sm 0.0991/0.1930 0.1210/0.2320 - 339 277 361 53.2 8300 PVC
STA
CT20P105A1 Four Core Cables with Reduced Neutral
Copper
PVC
240 sm + 120 sm 0.0754/0.1530 0.0840/0.1850 - 390 328 430 59.6 10550 PVC
STA
CT30P105A1 Four Core Cables with Reduced Neutral
Copper
PVC
300 sm + 150 sm 0.0601/0.1240 0.0770/0.1510 - 441 362 506 65.4 12920 PVC
STA
CT40P105A1 Four Core Cables with Reduced Neutral
Copper
PVC
400 sm + 240 sm 0.0470/0.0754 0.0606/0.084 - 502 421 575 70.8 16360 PVC
STA
  • For outdoor installations in damp wet locations where mechanical damages are expected to occur.
  • IEC 60502-1

Download the full specifications PDF for more info
SPECS PDF